IO Status and LockNode responsiveness - WaveNet

You can check the following:

  • Signal at the respective input
  • Results of the last broadcast for each device
  • Status of the outputs
  • Analogue voltage present

You can also switch the outputs manually.

NOTE

notice

Manual switching disabled

You can switch the output depending on identification media or completed reactions (see I/O configuration and protection functions). Outputs controlled by the IO configuration cannot be switched manually.

  1. WaveNet Manager opened via LSM (see Best Practice: From the LSM software)
  2. RouterNode supplied with power.
  3. RouterNode connected to WaveNet (see Add RouterNode to WaveNet).
  1. Click with the right mouse button on the entry of the RouterNode whose IO status you want to read out.
  2. The window Administration opens.
  3. In the area Maintenance select the option Set output and I/O status.
  4. The Administration window closes.
  1. The window I/O status opens.

Status of the inputs

In the area Status of inputs you can see the status of the inputs (valid for RN and RN2):

Status of the inputs

Meaning

Off

There is no signal at the input. The applied voltage is lower than the reference voltage.

On

A signal is present at the input. The applied voltage is higher than the reference voltage.

Comparison voltages (RN and RN2)

<0,9 VDC

LOW (no signal)

>2.1 VDC

HIGH (signal)

Status/responsiveness of the LockNodes

In the areaStatus of inputs you can also see the behaviour of the LockNodes during the last broadcast:

Error

No reply

Successful

Processing of the command in the LockNode of the locking device faulty.

There are two possibilities here:

  • Locking device with LockNode did not receive command and therefore did not respond.
  • Locking device with LockNode has received command but RouterNode has not received response.

The LockNode locking device has received the command and the RouterNode has received the response.

Status of the outputs

In the area Status and settings of outputs you can see the status of the outputs and can switch outputs manually.

Status of the inputs

Meaning

Output

Output is switched.

Output

Output is not switched.

  1. Activate the checkbox Output of the output that you want to switch or deactivate the checkbox Output that you no longer want to switch.
  2. Click on the button Set.
  3. The I/O status window closes.
  4. The window WaveNetManageropens.
  1. Output is switched.