Switching interval - SmartRelay 3 system
You can freely configure the duration of opening between 0 s and 25 s. The opening interval configured on the controller also applies to the SmartOutput modules.
IMPORTANT
Unintentional opening of the SmartOutput module
If a pulse length of 0 s has been configured in LSM, the SmartOutput module still activates for about three seconds.
NOTE
Long release by SmartOutput modules not supported
SmartOutput modules use the G1 protocol. The G1 protocol does not support the Long opening function. The SmartOutput modules used open for the time configured on the controller regardless of this setting on the transponder.
- Components wired correctly (see wiring).
- Components connected to power.
- Double-click on the SmartRelay 3 entry in the matrix to open the settings.
- Change to the Configuration/Data tab.
- Enter the desired pulse length.
- Click on the Apply button.
- Click on the Exit button.
- Execute programming (see Programming).
- Switching interval is set.