Connections - SmartRelay 3 system
NOTE
Fault through electromagnetic fields
Signals on the connection cable between reader and controller are influenced externally by electromagnetic fields. A shielded cable reduces the influence of disruptive signals from outside.
- Use a shielded cable.
Ground loop through shielding
Remote devices may have a slightly different ground potential. A shield connected on both sides represents a second ground connection through which this potential difference is compensated. The resulting current flow can interfere with the data transfer.
- Only connect the screen on one side to the common ground potential, e.g. on the reader (WP variant: Shield is led out on reader side together with ground).