Wiegand33 (for PRIMION connections) - SmartRelay AX Classic

Signal description

A Wiegand interface uses the following standardised signals:

Signal

Meaning

Explanation

SREL.ADV connection

SREL3 ADV connection

SREL AX Classic connection

D0

Data 0

F1 ("D0")

O1

Output 1

D1

Data 1

F2 ("D1")

O2

Output 2

All outputs are open-drain. A pull-up resistor (1kΩ to 10kΩ type) and the positive power supply (3 VDC to 24 VDC ) must be provided for signal lines.

The signals are “Active low”.

Signal timing

Time

Description

Min.

Typ.

Max.

Unit

tdL

Data bit pulse width

80

100

120

µs

tpI

Time between two bits (idle time)

800

900

1000

µs

tpP

Signal period (data rate period)

900

1000

1100

µs

Data format (Wiegand 33-bit)

This is a modified Wiegand format. It contains the complete 16-bit facility code (or locking system ID).

Bit number

Meaning

Bits 1 to 16

Facility code (0 to 65,535). Bit 1 is MSB.

Bits 17 to 32

User ID number (0 to 65,535). Bit 17 is MSB.

Bit 33