Testing the block lock function - VdS shunt lock
- Press an authorised transponder on an activation unit twice in quick succession (0.5 s to 2 s).
- LEDs on deactivation units go out.
- Acoustic acknowledgement of the activation request sounds:
Acknowledgement by activation master (jumper B1 on b/c): 2.5 s or
acknowledgement by burglar alarm system (jumper B1 on a/b): Dependent on burglar alarm system - Locking devices are deactivated.
- Alarm is activated.
- Check that the locking devices are deactivated.
- Press an authorised transponder on an activation unit twice again in quick succession (0.5 s to 2 s).
- Locking devices are activated.
- Activation unit signals that the locking devices have been activated:
Acknowledgement by activation master (jumper B1 on b/c): Single short-long flashes or
acknowledgement by burglar alarm system (jumper B1 on a/b): Double signal tone on activation unit - LEDs of the deactivation units light up again.
- Alarm system is deactivated.
- Locking devices are activated and can be switched again.
- Check that the locking devices are activated.
- Repeat this function test several times.
- Set jumper B1 to a/b, if not already done (VdS-compliant acknowledgement by burglar alarm system).
- Close the housing with the cover.
- Stick the supplied VdS stickers onto the slotted screws.
- Components can no longer be tampered with undetected (sealing of the screws).
- Block lock function is set up.