Switching contact - VdS shunt lock
You only need pins 5 to 7 (see Connections of the activation slave) of the activation slave if the burglar alarm system is to activate internally.
In case of internal activation, the burglar alarm system only evaluates the detectors of a partial area.
Wire the corresponding activation slave separately from other activation units and connect pins 5 to 7 to the internal activation connection of the burglar alarm system. The relay contact is not static, but acts for 1.2 s on the internal activation connection of the burglar alarm system.
Connect the switching contact to the alarm system. The alarm system should internally activate the corresponding section when the relay is energised. Please refer to the documentation of the burglar alarm system for wiring and any terminating resistors.

The contact bridges are equipped ex works as follows:
Contact bridge | Layout |
|---|---|
Rs | Open |
Ry | Wire jumper |
Rx | Wire jumper |
Rz | open, optional termination resistor |