Testing the deactivation unit - VdS shunt lock

  1. Connect the deactivation unit to a power supply (for example a 9V block battery, see Connections of deactivation unit).
  2. Position the deactivation unit next to the digital locking device (lock cylinder and SmartHandles max. 30 cm, SmartRelay 20 cm to 1 m).
  3. Make sure that all components are correctly programmed (see Programming).
  4. Connect pins 13 and 15 (temporarily).
  5. Lock is deactivated (beep at lock if necessary).
  6. LED on deactivation unit goes out.
  7. Lock no longer reacts to identification media.
  8. Disconnect pins 13 and 15 again.
  9. Locking device is activated (if necessary, signal tone on lock).
  10. LED on deactivation unit goes on.
  11. Lock reacts to identification media again.
  12. Repeat the test several times.
  13. Then carry out the installation as described (see Installing the deactivation unit and Connections of deactivation unit).